Catalogus GSI 2024

24 CATALOGUS 2024 ADVANTAGES ■ Valve made from high-quality, glass fiber-reinforced plastic, ideal for plastic systems ■ Can be used for various media ■ Inch standard thread: can be connected directly to plastic gland, no need for metal conversion adapters ■ Fast, precise adjustment with twist grip ■ High kVS values ■ Fast, simple assembly without tools TACOSETTER HYLINE BALANCING VALVE Direct adjustment, display and shutoff of flow in systems. 108 G 237 D 2 D 1 DIMENSIONAL DRAWING O-RING TYPE OVERVIEW TacoSetter Hyline | Balancing valve with external thread Order no. DN G × G Measuring range kVS (m3/h) 223.8410.000 25 1 ½" × 1 ½" 10 – 25 (l/min) 5.9 223.8411.000 25 1 ½" × 1 ½" 15 – 40 (l/min) 9.1 223.8412.000 25 1 ½" × 1 ½" 20 – 60 (l/min) 11.7 223.8523.000 32 2" × 2" 20 – 55 (l/min) 11.7 223.8524.000 32 2" × 2" 30 – 80 (l/min) 12.5 MEASUREMENT TABLE TacoSetter Hyline | Balancing valve with external thread Order no. DN G D1 D2 O-Ring 223.8410.000 25 1 ½" 29.7 36.4 29.82 × 2.62 223.8411.000 25 1 ½" 29.7 36.4 29.82 × 2.62 223.8412.000 25 1 ½" 29.7 36.4 29.82 × 2.62 223.8523.000 32 2" 36.0 42.7 36.10 × 3.53 223.8524.000 32 2" 36.0 42.7 36.10 × 3.53 0 2 4 6 20 0 -10 40 60 80 PRESSURE-TEMPERATURE CURVE Operating pressure (bar) Operating temperature (°C) 100 1000 1 10 100 10 1 100 1 10 100 10 1 A B B C DN32 A DN 32, 20 – 55 l/min B DN 32, 30 – 80 l/min Pressure loss (mbar) Pressure loss (mbar) Flow rate (l/min) A DN 25, 10 – 25 l/min B DN 25, 15 – 40 l/min C DN 25, 20 – 60 l/min PRESSURE LOSS DIAGRAMS DN25 Flow rate (l/min) A

RkJQdWJsaXNoZXIy MTkyODMyNw==